We're Hiring !​ Ready to join our team?​

Reflecta-Guard & Bradford Foil · Combined-System Top-Up Specialist

Reflective Foil Sarking for Brisbane Warehouses — Combined-System Top-Up Specialists

Reflective foil sarking is the combined-system top-up that takes a Brisbane warehouse roof from “almost there” to NCC
Section J compliant. Insulation Guru Brisbane installs
Reflecta-Guard
via GI Building Services and
CSR Bradford
medium-duty foil under metal roofing across Class 5–9 commercial buildings — radiant-heat reflection, vapour control
and a measured R0.7–R1.0 system contribution per layer that closes the gap to
NCC 2022 Part J4D4
Total R3.7 in Climate Zone 2. Paired with Bradford Anticon, Knauf Earthwool or Higgins polyester, our sarking installs
meet Section J Part J4 condensation-control intent under
AS/NZS 4859.1
and AS/NZS 4200.1. We do not install spray foam.

    Or call our commercial team: 0494 157 102

    R0.7–R1.0
    System contribution per sarking layer (air-gap dependent)

    $6–$12
    Indicative installed cost per square metre
    Insulation Guru Brisbane install ranges

    Part J4
    NCC condensation-control compliance pathway

    AS/NZS 4200.1
    Sarking material & installation standard

    What Is Reflective Foil Sarking

    Reflective Foil Sarking Defined — Radiant-Heat Barrier & Vapour Control Membrane

    Reflective foil sarking is a multi-layer aluminium-laminate membrane installed under metal roof sheeting (and
    sometimes wall cladding) to perform two coupled functions: reflect radiant heat that would otherwise transfer
    across the air gap between the roof sheet and the building interior, and act as a vapour control membrane that
    prevents internal moisture from condensing on the cool underside of the metal sheet at night.

    Unlike bulk insulation — Knauf Earthwool glasswool, CSR Bradford Anticon, Higgins polyester batts — sarking has
    negligible conductive R-value on its own. Aluminium foil is a near-perfect conductor; what foil does
    have is a very low emissivity (typically below 0.05 for unoxidised foil), meaning it reflects rather than radiates
    thermal energy. When installed against an air gap, that low-emissivity surface dramatically reduces the radiant
    heat transferred across the gap. The resulting system R-value contribution is R0.7–R1.0 per layer,
    depending on:

    • Air-gap depth — the cavity between the foil face and the next surface. Larger gaps deliver more radiant performance up to a thermal-convection ceiling.
    • Heat-flow direction — downward heat flow (summer roof condition in Brisbane) is the dominant case for warehouse roof spec.
    • Foil orientation — single-sided foil reflects on one face; double-sided reflects both directions, useful in cavity applications with two adjacent air gaps.
    • Surface condition — clean, unoxidised foil retains low emissivity. Dust, condensation residue and oxidation degrade performance over time, which is why sarking is installed inside the roof envelope, not exposed.

    The product carries AS/NZS 4859.1 thermal performance certification and is installed to AS/NZS 4200.1 — the
    pliable building membrane standard — with sealed laps and continuous coverage. Reflective foil sarking is also a
    NCC 2022 Part J4
    condensation-control measure — its third function, often the deciding spec driver, is preventing roof-cavity
    condensation that would otherwise drip into bulk insulation, corrode purlins and feed mould in lined ceilings below.

    Reflective foil sarking does three things at once on a Brisbane warehouse roof: radiant-heat reflection, vapour
    control, and Section J Total R-value top-up. It is rarely the only insulation in a Section J pathway —
    sarking pairs with Bradford Anticon, Knauf Earthwool or Higgins polyester to hit Total R3.7.

    When Sarking Is Required

    When NCC 2022 Section J Requires Sarking on a Brisbane Warehouse Roof

    Section J doesn’t always demand reflective foil sarking by name, but three independent triggers commonly result
    in sarking being specified for a Brisbane warehouse — and our role is to read the
    Section J report, identify which triggers apply, and install
    the right foil grade against the actual envelope assembly.

    Trigger 1 — Section J Part J4 Condensation Control Under Metal Roofing

    NCC 2022 Volume One Part J4
    includes condensation-control provisions for the building fabric. In Brisbane’s Climate Zone 2 — warm humid summer,
    mild winter — moist internal air rising into a roof cavity hits the cool metal sheet at night and condenses on
    the sheet underside. Without a vapour control layer on the warm (interior) side of the assembly, that condensation
    drips into bulk insulation, degrades the installed Total R-value over time, corrodes purlin fixings, and feeds
    mould growth in any lined ceiling below. Reflective foil sarking installed to AS/NZS 4200.1 with sealed laps
    satisfies the membrane requirement. Some DTS (Deemed-to-Satisfy) pathways require sarking even when bulk
    insulation alone would meet the R-value target
    , specifically because of Part J4 condensation control.

    Trigger 2 — Combined-System R-Value Top-Up to Hit Total R3.7

    The second trigger is mathematical. NCC 2022 Part J4D4 requires a Total R-value of R3.7 for a Climate Zone 2
    commercial roof (downward heat flow, all Class 5–9). Bradford Anticon 130 (R3.0 material) on its own falls
    short. Adding a layer of reflective foil sarking with a defined air gap contributes R0.7–R1.0 system
    R-value
    , taking the assembly to R3.7+ Total once air-film and framing-bridge contributions are accounted for
    per AS/NZS 4859.1. Sarking is the
    cheapest path-to-compliance when the bulk insulation specification is already locked but the system R-value
    audit shows a gap.

    Trigger 3 — Radiant Heat Reduction Under Metal Roofing

    Even setting Section J aside, radiant heat is the dominant heat-gain pathway through an uninsulated metal roof
    in a Brisbane summer. Roof-cavity temperatures regularly exceed 65°C in Climate Zone 2; a low-emissivity
    foil face under the sheet reflects the radiant component back rather than letting it re-radiate downward into
    the building. For occupied production zones, mezzanine offices and any operational space directly under metal
    sheeting, the radiant-comfort case is independent of the Section J calculation and often drives the decision
    to specify sarking.

    In practice, sarking is specified on roughly 70–80% of new-build Brisbane warehouse roofs we install, and on
    every roof recover where the metal sheet is being replaced. The combination of Bradford Anticon roofing blanket
    and reflective foil sarking is the single most common Brisbane warehouse roof system in our portfolio.

    Product Range — Reflecta-Guard

    Reflecta-Guard Reflective Foil via GI Building Services

    Reflecta-Guard,
    supplied via GI Building Services, is a multi-layer woven-foil reflective laminate purpose-built for Australian
    commercial roofing applications. The product runs in heavy-duty and medium-duty grades — the woven scrim
    reinforcement gives Reflecta-Guard tear strength during installation, important on commercial roofs where
    installers walk the foil on purlins under load and where lap detailing is critical to deliver the certified
    vapour control performance.

    Reflecta-Guard sits in the AS/NZS 4859.1 certified pliable-membrane category and installs to AS/NZS 4200.1.
    Insulation Guru Brisbane carries Reflecta-Guard as our default sarking on commercial roof recovers and on
    retrofit projects where installer handling load is high — the heavy-duty grade in particular is robust to the
    handling of a multi-bay warehouse re-sheet.

    • Heavy-duty grade — high tear strength, woven scrim reinforcement, default specification on commercial roof recovers and retrofits with high installer handling load.
    • Medium-duty grade — standard commercial spec for new-build warehouse roofs where the foil is laid once and immediately covered by Anticon and metal sheet.
    • Foil orientation options — single-sided and double-sided variants for different cavity assemblies. Double-sided is the right call where a second air gap below the bulk insulation creates a reflective cavity on the warm side of the lined ceiling.
    • Roll widths — sized for commercial purlin spacing; lap detailing per the Reflecta-Guard installation guide ensures continuous vapour control across the full roof envelope.

    When We Specify Reflecta-Guard

    Reflecta-Guard is our default on roof recovers — typical Class 7b warehouse stock from the 1980s and 1990s
    in Geebung,
    Banyo and
    Acacia Ridge reaching end-of-life on the original
    tin sheet. The heavy-duty grade is robust to the handling load of a multi-bay re-sheet, and GI Building Services
    stock availability is reliable for staged delivery on programmed projects.

    Product Range — CSR Bradford

    CSR Bradford Medium-Duty Reflective Foil Sarking

    CSR Bradford
    is the long-established Australian manufacturer of foil-laminate sarking, supplying medium-duty single-sided and
    double-sided foil products that pair directly with the Bradford Anticon roofing blanket range. Bradford’s
    reflective foil is the default specification on combined-system roof installs where the bulk insulation is already
    Bradford Anticon — the supply chain, lot numbers, AS/NZS 4859.1 certification and warranty path all sit inside
    the same Bradford supply pack.

    For Brisbane warehouse roof systems specifying Anticon 130 (R3.0 material) plus sarking to hit Section J Total
    R3.7, Bradford medium-duty foil paired with Anticon 130 is the single most common combined-system spec in our
    portfolio. Single-sided foil faces the building interior; double-sided is specified where the assembly creates
    a second reflective cavity on the warm side of the bulk insulation.

    • Bradford medium-duty foil-laminate — single-sided and double-sided options, AS/NZS 4859.1 certified, manufactured to AS/NZS 4200.1 pliable-building-membrane standard.
    • Pairs directly with Bradford Anticon — same supplier, same lot-tracking, same Section J verification pack.
    • Roll widths sized for commercial purlin spacing — lap detail per Bradford technical specification.
    • System R-value contribution — R0.7–R1.0 per layer depending on air gap and orientation, calculated to AS/NZS 4859.1.

    When We Specify Bradford Foil

    Bradford reflective foil is our default on new-build warehouse roofs already specifying Bradford Anticon —
    simplifying supply, lot tracking and the Section J compliance pack. For projects in the
    South West Industrial Gateway (Wacol, Acacia
    Ridge, Carole Park) and Yatala / Logan corridor, Bradford’s
    direct-supply availability into our coordinated install programs makes it the path of least resistance on
    programmed builder timelines.

    Both Reflecta-Guard and Bradford foil sit at the same AS/NZS 4859.1 / AS/NZS 4200.1 compliance baseline. The
    choice between them is driven by handling load (heavy-duty Reflecta-Guard for retrofits and recovers), supply
    coordination (Bradford foil paired with Bradford Anticon), and project-specific access. Both deliver R0.7–R1.0
    system contribution per layer.

    Comparison

    Sarking Alone vs Combined System — When Each Is Sufficient

    The most common spec question we see on Brisbane commercial projects: can reflective foil sarking do the job by
    itself, or does the project need bulk insulation as well? The answer depends on the BCA class, whether Section J
    applies, and what the Total R-value target is.

    Building scenarioSarking alone sufficient?Combined system required?Insulation Guru spec
    Class 5/6/7b/8/9b commercial warehouse, NCC Section J applies, Climate Zone 2No — sarking alone delivers R0.7–R1.0, well short of Total R3.7Yes — sarking + bulk insulationBradford Anticon 130 (R3.0) + Bradford foil OR Reflecta-Guard sarking → R3.7+ Total
    Class 7b storage shed, light-duty, Section J exempt or BCA Class 10a (non-habitable)Often yes — radiant comfort only, no Section J targetOptional, depends on operational useReflecta-Guard medium-duty as standalone radiant barrier
    Open-sided agricultural shed / rural farm shed (no Section J)Yes — sarking is the default specNoReflecta-Guard or Bradford foil, sarking-only spec
    Class 5 office / Class 6 retail, Section J applies, single-layer install desiredNoCombined system; consider Anticon HP 130 (R3.6) to reduce sarking dependencyAnticon HP 130 + sarking for redundancy and Part J4 condensation control
    Roof recover on 1990s warehouse, Section J retrofit assessmentNoYes — recover triggers full envelope reviewReflecta-Guard heavy-duty + Anticon 130 during re-sheet
    Cold storage / refrigerated warehouse, Class 8No — vapour control critical, R-values much higher than Section J floorYes — but spec moves to insulated panel systems (BondorPanel / ASKIN)See Cold Storage Insulation Brisbane

    The decision tree is simple: if Section J applies and the building is a Class 5–9 commercial structure, sarking
    alone is not enough. If Section J doesn’t apply (or the building is a Class 10a non-habitable shed), sarking
    alone is often the right answer for radiant-comfort spec. Insulation Guru Brisbane reads the Section J report
    first, then matches the spec.

    Sarking Variants & Pairings

    Six Reflective Foil Sarking System Configurations

    Combined-System Default
    Bradford Foil + Bradford Anticon 130

    The single most common Brisbane warehouse roof spec we install. CSR Bradford medium-duty single-sided foil
    paired with Bradford Anticon 130 (R3.0 glasswool) under metal sheeting. System R-value: R3.7+ Total in Climate
    Zone 2, satisfying NCC 2022 Part J4D4. Bonus: Part J4 condensation control via the foil vapour membrane.
    Cost: $6–$12/m² (sarking only) or $26–$42/m² (combined system, sarking + Anticon installed). Lot numbers
    recorded for the Section J verification pack.

    Heavy-Duty Retrofit
    Reflecta-Guard Heavy-Duty + Anticon 130

    Default spec for roof recovers on 1980s and 1990s Class 7b stock — the tear-resistant woven scrim of
    Reflecta-Guard heavy-duty handles the load of a multi-bay re-sheet program. Same combined-system R3.7+
    system result as the Bradford pairing; supply runs through GI Building Services. Cost: $7–$13/m² (sarking only).

    Single-Layer Section J Pathway
    Sarking + Anticon HP 130 (R3.6)

    Where the Section J consultant has specified Anticon High Performance HP 130 as a single-layer R3.6 system,
    sarking is still installed for Part J4 condensation control and as an envelope-redundancy layer. The R-value
    system isn’t dependent on the sarking contribution but the membrane function still matters under metal
    sheeting in Brisbane’s Climate Zone 2. Cost: $6–$12/m² (sarking only).

    Double-Sided Cavity Assembly
    Bradford Double-Sided Foil + Lined Ceiling

    Where the warehouse has a lined ceiling below the structural roof — Class 5 office areas, mezzanine offices,
    breakroom annexes — double-sided foil delivers reflective performance into both the roof cavity above and the
    lined-ceiling cavity below. Pairs with Knauf Earthwool R3.5–R4.0 batts in the lined-ceiling cavity. Cost:
    $7–$13/m² (sarking only).

    Sarking-Only (Non-Section-J)
    Reflecta-Guard Medium-Duty Standalone

    Class 10a non-habitable sheds, agricultural buildings, open carports and other Section-J-exempt structures
    where the spec is purely radiant-comfort driven. Reflecta-Guard medium-duty installed alone, R0.7–R1.0
    system R-value, no bulk insulation. The right spec only when Section J doesn’t apply. Cost: $6–$10/m².

    Recover + Wall Wrap
    Sarking + Wall Foil Continuous Envelope

    Continuous-envelope spec where sarking under the metal roof transitions to reflective wall-wrap behind tilt
    panel or framed cladding — a continuous vapour-control and radiant-barrier layer per NCC 2022 Part J4D3(1).
    Pairs with Knauf Earthwool batts in framed wall cavities or insulated-panel walls. Often specified on
    food-grade and pharma-grade Class 8 facilities where envelope continuity is operational, not just regulatory.

    What we don’t install: Insulation Guru Brisbane does not install spray foam (open-cell or
    closed-cell polyurethane) — including sprayed reflective coatings or polyurethane-based vapour barrier systems.
    Reflective foil sarking from Reflecta-Guard or CSR Bradford is the AS/NZS 4859.1 / AS/NZS 4200.1 traditional-
    material pathway for radiant-heat reduction, vapour control and Part J4 condensation control without
    polyurethane chemistry.

    Investment

    Reflective Foil Sarking — Indicative Pricing

    Warehouse sizeSarking only (Reflecta-Guard or Bradford)Sarking + Anticon 130 (combined system)Sarking + Anticon HP 130
    500 m² (small workshop)$3,000–$6,000$13,000–$17,000$14,000–$19,000
    1,000 m² (typical SME warehouse)$6,000–$12,000$24,000–$32,000$28,000–$36,000
    2,500 m² (mid-size DC)$15,000–$28,000$58,000–$78,000$66,000–$88,000
    5,000 m² (large DC / 3PL)$28,000–$55,000$110,000–$155,000$125,000–$175,000

    All prices ex GST. Sarking-only ranges $6–$12/m² (medium-duty) to $7–$13/m² (heavy-duty Reflecta-Guard). Combined-
    system pricing assumes the bulk-insulation layer (Bradford Anticon) is installed in the same install pass, which
    is how new-build and roof-recover programs are programmed. Final quote subject to site survey, access, purlin
    condition and Section J target.

    Our Process

    Sarking Spec to Sign-Off — Four Steps

    01
    Section J Read & Spec

    We read the architect’s Section J DTS or JV3 report, confirm whether sarking is mandated by Part J4
    condensation control, identify the bulk-insulation pairing target, and recommend Reflecta-Guard or Bradford
    based on access and coordination.

    02
    Coordinated Supply

    Order from GI Building Services
    (Reflecta-Guard) or
    CSR Bradford
    direct. Lot numbers and AS/NZS 4859.1 / AS/NZS 4200.1 compliance certificates recorded for the Section J pack.
    Staged delivery so foil isn’t exposed before deployment.

    03
    Installation to AS/NZS 4200.1

    Sarking laid foil-face down across purlins, laps sealed with foil tape per manufacturer’s spec, continuous
    coverage. White Card holders, your-site SWMS, full
    WorkSafe Queensland-compliant safety systems.

    04
    Verification & Sign-Off

    Post-install verification: installed Total R-value, sarking grade with lot numbers, lap detail compliance,
    combined-system R-value calculation. Suitable for certifier hand-over. Defects period: 12 months on workmanship.

    Service Footprint

    Brisbane Industrial Corridors — Where We Install Sarking

    Reflective foil sarking installs span the full
    Brisbane warehouse insulation service area — every roof recover
    and every new-build with metal roofing across Class 5–9 commercial stock. Highest-volume corridors:

    South West Industrial Gateway — Wacol & Surrounds

    The largest commercial warehouse stock in SEQ. Anchored by
    Wacol (Metroplex Estate),
    Acacia Ridge,
    Carole Park and
    Parkinson. Bradford foil + Anticon 130 is the
    default combined-system spec.

    Australia TradeCoast — Port + Airport

    Logistics-heavy 24/7 operations across
    Eagle Farm,
    Pinkenba,
    Lytton and
    Brisbane Airport. High condensation-control
    priority because of operational humidity loads — Part J4 sarking spec is rarely optional.

    Yatala / Logan Corridor — M1 Distribution

    Large-format DCs and cold-logistics belt across
    Yatala,
    Crestmead,
    Berrinba and
    Stapylton. Combined Bradford foil + Anticon 130
    on new builds; Reflecta-Guard heavy-duty on recovers.

    Northern Industrial — Geebung-Banyo Belt

    Tight 1980s–1990s stock reaching end-of-life on roof recovers across
    Geebung,
    Banyo and
    Brendale — Reflecta-Guard heavy-duty is the default
    spec for this corridor’s recover programs.

    What Commercial Clients Get

    Documentation, Insurance, Coordination — Standard

    • Insurance: Public Liability cover and Workers Compensation in force per WorkSafe Queensland; certificates issued on request before site mobilisation.
    • Compliance documentation: Section J verification pack including sarking lot numbers, AS/NZS 4859.1 thermal certification, AS/NZS 4200.1 pliable-membrane compliance, installed lap detail records.
    • Combined-system R-value calculation: Total R-value calculated per AS/NZS 4859.1 with sarking system contribution, bulk insulation R-value, air-film and framing-bridge contributions.
    • Defects period: 12 months on workmanship; manufacturer’s warranty on materials per Reflecta-Guard / GI Building Services and CSR Bradford terms.
    • Coordination with builders & consultants: direct coordination with principal contractor, Section J consultant and certifier — no middle-man.
    • Continuous envelope: sarking continuous across the full roof per NCC 2022 Part J4D3(1) — no gaps at penetrations, no breaks at structural lines, lap detail per manufacturer specification.

    FAQ

    Reflective Foil Sarking Brisbane — Frequently Asked

    Almost never on its own for an NCC Section J compliant building. Reflective foil sarking contributes R0.7–R1.0 of system R-value per layer depending on air-gap depth and orientation — well short of the Total R3.7 required for a Climate Zone 2 commercial roof under NCC 2022 Part J4D4. Sarking-alone installs are limited to non-Section-J pathways: light-duty open sheds, carports, agricultural buildings, or as a radiant-heat barrier on existing roofs where the building is exempt from Section J or the spec is purely radiant-comfort driven. For any Class 5–9 commercial warehouse, sarking is paired with bulk insulation — Bradford Anticon, Knauf Earthwool or Higgins polyester — to hit Total R3.7.

    No. Foil sarking and bulk insulation work on different physics. Sarking blocks radiant heat transfer (the dominant pathway across an air gap under a hot metal roof). Bulk insulation — Knauf Earthwool glasswool, Bradford Anticon, Higgins polyester — blocks conductive heat transfer through framed cavities and slows convective transfer through the bulk material. NCC Section J Total R-value is calculated against both pathways. A foil-only system delivers R0.7–R1.0; a bulk-only system misses the radiant pathway under metal roofs. The combined system — sarking plus Anticon 130 or equivalent — is what hits Section J Total R3.7 reliably.

    Sarking rolls out across the purlins, foil face down toward the building interior, with overlaps sealed by foil tape per AS/NZS 4200.1 installation guidance. Overlap is typically 100–150mm per the manufacturer’s specification (Reflecta-Guard or CSR Bradford). The metal roof sheet — Colorbond, Trimdek or Kliplok — fixes down over the top, leaving a small air gap between the foil face and the sheet underside. That air gap is what gives the foil its radiant-heat reduction performance. On a combined-system warehouse, Bradford Anticon roofing blanket sits over the sarking with the Anticon foil face also into the building, delivering radiant reduction at two surfaces plus glasswool conductive R-value plus rain acoustic absorption — a one-pass install for the roof envelope.

    Sarking acts as a vapour control membrane under the metal roof sheet. In Brisbane’s Climate Zone 2 — warm humid summer — moist internal air migrating up through a roof assembly hits the cool underside of the metal sheet at night and condenses. Without a vapour control layer, that condensation drips into bulk insulation (degrading R-value), corrodes purlins, and feeds mould growth in lined ceilings below. NCC 2022 Section J Part J4 includes condensation-control provisions — sarking installed to AS/NZS 4200.1 with sealed laps satisfies the membrane requirement on the warm side of the assembly. Some DTS (Deemed-to-Satisfy) pathways require sarking even when bulk insulation alone meets the R-value target, specifically for condensation control.

    Both are AS/NZS 4859.1 certified reflective foil laminates. Reflecta-Guard, supplied via GI Building Services, runs a multi-layer woven-foil construction with heavy-duty and medium-duty product grades — popular on commercial roofs where tear strength during installation is critical and on retrofit projects where the foil sees handling load. CSR Bradford reflective foil is the long-established Australian medium-duty foil-laminate, available single-sided and double-sided, frequently specified alongside Bradford Anticon roofing blanket as a paired system. Insulation Guru Brisbane specifies the product to match the roof system, the installer access, and the supplier coordination — both meet NCC Section J Part J4 condensation-control intent and both deliver R0.7–R1.0 system contribution per layer. We do not install spray foam — we install Knauf, Bradford, Higgins, Reflecta-Guard and cellulose only.

    Reflective foil sarking contributes R0.7–R1.0 of Total system R-value per layer, depending on the depth of the adjacent reflective air gap (the cavity between foil face and the next surface), the orientation of heat flow (downward in summer roof condition), and whether the foil is single-sided or double-sided. The number is not a material R-value — foil itself has near-zero conductive R — it is the air-gap radiant performance per AS/NZS 4859.1 calculation. In a combined system with Bradford Anticon 130 (R3.0 material), the sarking layer takes the system from ~R3.0 toward R3.7+ Total, hitting NCC 2022 Part J4D4 Climate Zone 2 compliance.

    Only as part of a roof recover — the foil installs between purlin and metal roof sheet, so the sheet has to be off the building for the install. We routinely sarking and re-blanket warehouses in Brisbane during scheduled re-roofing programs, particularly across the older Class 7b stock in Geebung, Banyo and Acacia Ridge where 1980s and 1990s tin roofs are reaching end-of-life. For retrofit projects where the roof isn’t being re-sheeted, the alternative is Knauf Earthwool batts or Higgins polyester batts in the ceiling cavity — bulk insulation only, no radiant barrier — which doesn’t deliver the same Section J pathway but is the only practical option without removing the roof sheet.

    No. Insulation Guru Brisbane does not install spray foam (open-cell or closed-cell polyurethane). Where spray foam has been specified for radiant control or condensation control under metal roofing, we recommend the equivalent traditional-material pathway: Reflecta-Guard or CSR Bradford reflective foil sarking for the radiant and vapour control layer, plus Bradford Anticon roofing blanket for the bulk insulation layer. The combined system delivers NCC 2022 Section J Total R3.7 in Climate Zone 2 using AS/NZS 4859.1 certified materials with established Bradford and GI Building Services manufacturer warranty pathways — no polyurethane chemistry.

    Talk to Our Commercial Team

    Specifying sarking for a Brisbane warehouse roof?

    Insulation Guru Brisbane’s commercial team can read your Section J report, recommend the right Reflecta-Guard or
    CSR Bradford foil grade for your roof system, and install to AS/NZS 4200.1 with full Part J4 condensation-control
    documentation — no spray foam, no polyurethane, just AS/NZS 4859.1 certified traditional materials.

      Or call our commercial team: 0494 157 102

      Call Now